American Ductile Iron Pipe ANSI/AWWA C150/A21.50 and ANSI/AWWA C151/A21.51 Standard Pressure Classes - Wall Thickness and Nominal Wall Thicknesses
To Top of Page

ADIP Table No. 3-8
Size
in. |
Outside
Diameter
in. |
Pressure Class |
| 150 |
200 |
250 |
300 |
350 |
| Nominal Thickness in inches |
| 4 |
4.8 |
- |
- |
- |
- |
0.25 |
| 6 |
6.9 |
- |
- |
- |
- |
0.25 |
| 8 |
9.05 |
- |
- |
- |
- |
0.25 |
| 10 |
11.1 |
- |
- |
- |
- |
0.26 |
| 12 |
13.2 |
- |
- |
- |
- |
0.28 |
| 14 |
15.3 |
- |
- |
0.28 |
0.3 |
0.31 |
| 16 |
17.4 |
- |
- |
0.3 |
0.32 |
0.34 |
| 18 |
19.5 |
- |
- |
0.31 |
0.34 |
0.36 |
| 20 |
21.6 |
- |
- |
0.33 |
0.36 |
0.38 |
| 24 |
25.8 |
- |
0.33 |
0.37 |
0.4 |
0.43 |
| 30 |
32 |
0.34 |
0.38 |
0.42 |
0.45 |
0.49 |
| 36 |
38.3 |
0.38 |
0.42 |
0.47 |
0.51 |
0.56 |
| 42 |
44.5 |
0.41 |
0.47 |
0.52 |
0.57 |
0.63 |
| 48 |
50.8 |
0.46 |
0.52 |
0.58 |
0.64 |
0.7 |
| 54 |
57.56 |
0.51 |
0.58 |
0.65 |
0.72 |
0.79 |
| 60 |
61.61 |
0.54 |
0.61 |
0.68 |
0.76 |
0.83 |
| 64 |
65.67 |
0.56 |
0.64 |
0.72 |
0.8 |
0.87 |
Notes:
Pressure classes are defined as the rated water working pressure of the pipe in psi. The thicknesses shown are adequate for the rated water working pressure plus a surge allowance of 100 psi. Calculations result in net thicknesses and are based on a minimum yield strength in tension of 42,000 psi and 2.0 safety factor times the sum of working pressure and 100 psi surge allowance.
Thickness can be calculated for rated water working pressure and surges other than the above by use of equation 1 in ANSI/AWWA C150/A21.50.
AMERICAN Ductile Iron pipe is available for water working pressures greater than 350 psi. Check AMERICAN for details.
These are standard pressure classes as given in AWWA C150 and C151. AMERICAN can furnish any thickness in between these standard thicknesses if deemed economical for major projects.
AMERICAN Ductile Iron pipe is also available with thicknesses greater than Pressure Class 350. For special applications, contact AMERICAN.
American Ductile Iron FastiteĀ® Joint Pipe ANSI/AWWA C151/A21.51 Weights for Pressure Classes
To Top of Page
ADIP Table No. 3-9
Size
in. |
Pressure
Class |
Wall
Thickness
in. |
Weight in Pounds |
Per Foot
Plain End |
FASTITE JOINT |
Per Foot Inc. Bell |
Per Nominal* Length |
| 4 |
350 |
0.25 |
10.9 |
11.3 |
206 |
| 6 |
350 |
0.25 |
16 |
16.7 |
335 |
| 8 |
350 |
0.25 |
21.1 |
22.1 |
445 |
| 10 |
350 |
0.26 |
27.1 |
28.4 |
570 |
| 12 |
350 |
0.28 |
34.8 |
36.4 |
730 |
| 14 |
250 |
0.28 |
40.4 |
43.2 |
865 |
| 14 |
300 |
0.3 |
43.3 |
46.1 |
925 |
| 14 |
350 |
0.31 |
44.7 |
47.6 |
955 |
| 16 |
250 |
0.3 |
49.3 |
52.5 |
1050 |
| 16 |
300 |
0.32 |
52.5 |
55.7 |
1115 |
| 16 |
350 |
0.34 |
55.8 |
59 |
1180 |
| 18 |
250 |
0.31 |
57.2 |
60.8 |
1220 |
| 18 |
300 |
0.34 |
62.6 |
66.3 |
1330 |
| 18 |
350 |
0.36 |
66.2 |
69.8 |
1400 |
| 20 |
250 |
0.33 |
67.5 |
71.5 |
1435 |
| 20 |
300 |
0.36 |
73.5 |
77.5 |
1555 |
| 20 |
350 |
0.38 |
77.5 |
81.5 |
1635 |
| 24 |
200 |
0.33 |
80.8 |
85.6 |
1715 |
| 24 |
250 |
0.37 |
90.5 |
95.3 |
1910 |
| 24 |
300 |
0.4 |
97.7 |
102.5 |
2055 |
| 24 |
350 |
0.43 |
104.9 |
109.7 |
2200 |
| 30 |
150 |
0.34 |
103.5 |
111.7 |
2240 |
| 30 |
200 |
0.38 |
115.5 |
123.7 |
2480 |
| 30 |
250 |
0.42 |
127.5 |
135.7 |
2720 |
| 30 |
300 |
0.45 |
136.5 |
144.7 |
2900 |
| 30 |
350 |
0.49 |
148.4 |
156.6 |
3140 |
| 36 |
150 |
0.38 |
138.5 |
149.2 |
2990 |
| 36 |
200 |
0.42 |
152.9 |
163.6 |
3280 |
| 36 |
250 |
0.47 |
170.9 |
181.6 |
3640 |
| 36 |
300 |
0.51 |
185.3 |
196 |
3930 |
| 36 |
350 |
0.56 |
203.2 |
213.9 |
4285 |
| 42 |
150 |
0.41 |
173.8 |
188.3 |
3765 |
| 42 |
200 |
0.47 |
198.9 |
213.3 |
4265 |
| 42 |
250 |
0.52 |
219.9 |
234.3 |
4685 |
| 42 |
300 |
0.57 |
240.7 |
255.2 |
5105 |
| 42 |
350 |
0.63 |
265.7 |
280.2 |
5605 |
| 48 |
150 |
0.46 |
222.6 |
240.3 |
4805 |
| 48 |
200 |
0.52 |
251.3 |
269 |
5380 |
| 48 |
250 |
0.58 |
280 |
297.7 |
5955 |
| 48 |
300 |
0.64 |
308.6 |
326.3 |
6525 |
| 48 |
350 |
0.7 |
337.1 |
354.8 |
7095 |
| 54 |
150 |
0.51 |
279.7 |
301.7 |
6035 |
| 54 |
200 |
0.58 |
317.7 |
339.7 |
6795 |
| 54 |
250 |
0.65 |
355.6 |
377.5 |
7550 |
| 54 |
300 |
0.72 |
393.4 |
415.3 |
8305 |
| 54 |
350 |
0.79 |
431.1 |
453.1 |
9060 |
| 60 |
150 |
0.54 |
317 |
346.4 |
6930 |
| 60 |
200 |
0.61 |
357.7 |
387.1 |
7740 |
| 60 |
250 |
0.68 |
398.3 |
427.7 |
8555 |
| 60 |
300 |
0.76 |
444.6 |
474 |
9480 |
| 60 |
350 |
0.83 |
485 |
514.4 |
10290 |
| 64 |
150 |
0.56 |
350.5 |
386.1 |
7720 |
| 64 |
200 |
0.64 |
400.1 |
435.7 |
8715 |
| 64 |
250 |
0.72 |
449.6 |
485.2 |
9705 |
| 64 |
300 |
0.8 |
498.9 |
534.5 |
10690 |
| 64 |
350 |
0.87 |
542 |
577.6 |
11550 |
Notes:
1. * 4" Fastite pipes are furnished in 18-foot nominal lengths weights for all other sizes are for 20-foot nominal lengths.
2. Dimensions, lengths and weights, etc., are subject to change at our option.
Also see Standard Dimensions for Fastite Joint Pipe.

60" AMERICAN FastiteĀ® Joint Ductile Iron pipe being installed as a water transmission main.
AMERICAN Ductile Iron Pipe for Water or Other Liquids ANSI/AWWA C151/A21.51 Working Pressures and Maximum Depths of Cover for Minimum Pressure Classes of Ductile Iron Pipe 4" - 64"
To Top of Page

ADIP Table No. 3-10
Size
in. |
Pressure
Class |
Thickness
in. |
Working
Pressure (1)
psi |
Laying Conditions
Maximum Depth of Cover in Feet(2) |
| Type 1 |
Type 2 |
Type 3 |
Type 4 |
Type 5 |
| 4 |
350 |
0.25 |
350 |
53 |
61 |
69 |
85 |
100(3) |
| 6 |
350 |
0.25 |
350 |
26 |
31 |
37 |
47 |
65 |
| 8 |
350 |
0.25 |
350 |
16 |
20 |
25 |
34 |
50 |
| 10 |
350 |
0.26 |
350 |
11** |
15 |
19 |
28 |
45 |
| 12 |
350 |
0.28 |
350 |
10** |
15 |
19 |
28 |
44 |
| 14 |
250 |
0.28 |
250 |
* |
11** |
15 |
23 |
36 |
| 16 |
250 |
0.3 |
250 |
* |
11** |
15 |
24 |
34 |
| 18 |
250 |
0.31 |
250 |
* |
10** |
14 |
22 |
31 |
| 20 |
250 |
0.33 |
250 |
* |
10 |
14 |
22 |
30 |
| 24 |
200 |
0.33 |
200 |
* |
8** |
12 |
17 |
25 |
| 30 |
150 |
0.34 |
150 |
* |
- |
9 |
14 |
22 |
| 36 |
150 |
0.38 |
150 |
* |
- |
9 |
14 |
21 |
| 42 |
150 |
0.41 |
150 |
* |
- |
9 |
13 |
20 |
| 48 |
150 |
0.46 |
150 |
* |
- |
9 |
13 |
20 |
| 54 |
150 |
0.51 |
150 |
* |
- |
9 |
13 |
20 |
| 60 |
150 |
0.54 |
150 |
* |
5** |
9 |
13 |
20 |
| 64 |
150 |
0.56 |
150 |
* |
5** |
9 |
13 |
20 |
Notes:
-
These pipes are adequate for the rated working pressure plus a surge allowance of 100 psi. Ductile iron pipe for working pressures higher than 350 psi is available. Figures include 2.0 safety factor times the sum of working pressure and 100 psi surge allowance.
-
An allowance for single H-20 truck with 1.5 impact factor is included for all sizes and all depths of cover.
-
Calculated maximum depth of cover exceeds 100'.
* Laying condition Type 1 is limited to 12" and smaller pipe. For 14" and larger pipe, laying condition Type 1 should not be used.
** Minimum allowable depth of cover is 3'.
AMERICAN Ductile Iron Pipe for Water or Other Liquids ANSI/AWWA C151/A21.51 Working Pressures and Maximum Depths of Cover for Pressure Classes
To Top of Page

ADIP Table No. 3-11
Size
in. |
Pressure (1)
Class
psi |
Nominal
Thickness
in. |
Laying Conditions
Maximum Depth of Cover in Feet (2) |
| Type 1 |
Type 2 |
Type 3 |
Type 4 |
Type 5 |
| 4 |
350 |
0.25 |
53 |
61 |
69 |
85 |
100 (3) |
| 6 |
350 |
0.25 |
23 |
31 |
37 |
47 |
65 |
| 8 |
350 |
0.25 |
16 |
20 |
25 |
34 |
50 |
| 10 |
350 |
0.26 |
11** |
15 |
19 |
28 |
45 |
| 12 |
350 |
0.28 |
10** |
15 |
19 |
28 |
44 |
| 14 |
250 |
0.28 |
++ |
11** |
15 |
23 |
36 |
| 14 |
300 |
0.3 |
++ |
13 |
17 |
26 |
42 |
| 14 |
350 |
0.31 |
++ |
14 |
19 |
27 |
44 |
| 16 |
250 |
0.31 |
++ |
11** |
15 |
24 |
34 |
| 16 |
300 |
0.32 |
++ |
13 |
17 |
26 |
39 |
| 16 |
350 |
0.34 |
++ |
15 |
20 |
28 |
44 |
| 18 |
250 |
0.31 |
++ |
10** |
14 |
22 |
31 |
| 18 |
300 |
0.34 |
++ |
13 |
17 |
26 |
36 |
| 18 |
350 |
0.36 |
++ |
15 |
19 |
28 |
41 |
| 20 |
250 |
0.33 |
++ |
10 |
14 |
22 |
30 |
| 20 |
300 |
0.36 |
++ |
13 |
17 |
26 |
35 |
| 20 |
350 |
0.38 |
++ |
15 |
19 |
28 |
38 |
| 24 |
200 |
0.33 |
++ |
8** |
12 |
17 |
25 |
| 24 |
250 |
0.37 |
++ |
11 |
15 |
20 |
29 |
| 24 |
300 |
0.4 |
++ |
13 |
17 |
24 |
32 |
| 24 |
350 |
0.43 |
++ |
15 |
19 |
28 |
37 |
| 30 |
150 |
0.34 |
++ |
- |
9 |
14 |
22 |
| 30 |
200 |
0.38 |
++ |
8*** |
12 |
16 |
24 |
| 30 |
250 |
0.42 |
++ |
11 |
15 |
19 |
27 |
| 30 |
300 |
0.45 |
++ |
12 |
16 |
21 |
29 |
| 30 |
350 |
0.49 |
++ |
15 |
19 |
25 |
33 |
| 36 |
150 |
0.38 |
++ |
- |
9 |
14 |
21 |
| 36 |
200 |
0.42 |
++ |
8*** |
12 |
15 |
23 |
| 36 |
250 |
0.47 |
++ |
10 |
14 |
18 |
25 |
| 36 |
300 |
0.51 |
++ |
12 |
16 |
20 |
28 |
| 36 |
350 |
0.56 |
++ |
15 |
19 |
24 |
32 |
| 42 |
150 |
0.41 |
++ |
- |
9 |
13 |
20 |
| 42 |
200 |
0.47 |
++ |
8 |
12 |
15 |
22 |
| 42 |
250 |
0.52 |
++ |
10 |
14 |
17 |
25 |
| 42 |
300 |
0.57 |
++ |
12 |
16 |
20 |
27 |
| 42 |
350 |
0.63 |
++ |
15 |
19 |
23 |
32 |
| 48 |
150 |
0.46 |
++ |
- |
9 |
13 |
20 |
| 48 |
200 |
0.52 |
++ |
8 |
11 |
15 |
22 |
| 48 |
250 |
0.58 |
++ |
10 |
13 |
17 |
24 |
| 48 |
300 |
0.64 |
++ |
12 |
15 |
19 |
27 |
| 48 |
350 |
0.7 |
++ |
15 |
18 |
22 |
30 |
| 54 |
150 |
0.51 |
++ |
- |
9 |
13 |
20 |
| 54 |
200 |
0.58 |
++ |
8 |
11 |
14 |
22 |
| 54 |
250 |
0.65 |
++ |
10 |
13 |
16 |
24 |
| 54 |
300 |
0.72 |
++ |
13 |
15 |
19 |
27 |
| 54 |
350 |
0.79 |
++ |
15 |
18 |
22 |
30 |
| 60 |
150 |
0.54 |
++ |
5** |
9 |
13 |
20 |
| 60 |
200 |
0.61 |
++ |
8 |
11 |
14 |
22 |
| 60 |
250 |
0.68 |
++ |
10 |
13 |
16 |
24 |
| 60 |
300 |
0.76 |
++ |
13 |
15 |
19 |
26 |
| 60 |
350 |
0.83 |
++ |
15 |
18 |
22 |
30 |
| 64 |
150 |
0.23 |
++ |
2** |
9 |
13 |
20 |
| 64 |
200 |
0.64 |
++ |
8 |
11 |
14 |
21 |
| 64 |
250 |
0.72 |
++ |
10 |
13 |
16 |
24 |
| 64 |
300 |
0.8 |
++ |
12 |
15 |
19 |
26 |
| 64 |
350 |
0.87 |
++ |
15 |
17 |
21 |
29 |
Notes:
- These pipes are adequate for the rated working pressure indicated for each nominal size plus a surge allowance of 100 psi. Calculations are based on a 2.0 safety factor times the sum of working pressure and 100 psi surge allowance. Ductile iron pipe for working pressures higher than 350 psi is available.
- An allowance for a single H-20 truck with 1.5 impact factor is included for all sizes and all depths of cover.
- Calculated maximum depth of cover exceeds 100'.
++ Laying condition Type 1 is limited to 12" and smaller pipe. For 14" and larger pipe, laying condition Type 1 should not be used.
** Minimum allowable depth of cover is 3'.
AMERICAN Ductile Iron Fastite Joint Gravity Sewer Pipe ASTM A746 PIPE WITH FLEXIBLE LININGS
Depths of Cover for Standard Pressure Classes
To Top of Page
ADIP Table No. 3-14
Size
in. |
Pressure
Class
psi |
Thickness
in. |
Laying Conditions
Maximum Depth of Cover in Feet |
| Type 1 |
Type 2 |
Type 3 |
Type 4 |
Type 5 |
| 4 |
350 |
.25 |
53 |
61 |
69 |
85 |
109 |
| 6 |
350 |
.25 |
26 |
31 |
37 |
47 |
65 |
| 8 |
350 |
.25 |
16 |
20 |
25 |
34 |
50 |
| 10 |
350 |
.26 |
11** |
15 |
19 |
28 |
45 |
| 12 |
350 |
.28 |
10** |
15 |
19 |
28 |
44 |
| 14 |
250 |
.28 |
- |
11** |
15 |
23 |
41 |
| 14 |
300 |
.30 |
- |
13 |
17 |
26 |
43 |
| 14 |
350 |
.31 |
- |
14 |
19 |
27 |
44 |
| 16 |
250 |
.30 |
- |
11** |
15 |
24 |
41 |
| 16 |
300 |
.32 |
- |
13 |
17 |
26 |
43 |
| 16 |
350 |
.34 |
- |
15 |
20 |
28 |
45 |
| 18 |
250 |
.31 |
- |
10** |
14 |
23 |
40 |
| 18 |
300 |
.34 |
- |
13 |
17 |
26 |
43 |
| 18 |
350 |
.36 |
- |
15 |
19 |
28 |
45 |
| 20 |
250 |
.33 |
- |
10* |
14 |
23 |
40 |
| 20 |
300 |
.36 |
- |
13 |
17 |
26 |
43 |
| 20 |
350 |
.38 |
- |
15 |
19 |
28 |
44 |
| 24 |
200 |
.33 |
- |
8** |
12 |
20 |
37 |
| 24 |
250 |
.37 |
- |
11 |
15 |
23 |
41 |
| 24 |
300 |
.40 |
- |
13 |
17 |
26 |
43 |
| 24 |
350 |
.43 |
- |
15 |
19 |
28 |
45 |
| 30 |
150 |
.34 |
- |
- |
9** |
17 |
33 |
| 30 |
200 |
.38 |
- |
8** |
12 |
20 |
37 |
| 30 |
250 |
.42 |
- |
11 |
15 |
23 |
40 |
| 30 |
300 |
.45 |
- |
12 |
16 |
25 |
42 |
| 30 |
350 |
.49 |
- |
15 |
19 |
28 |
44 |
| 36 |
150 |
.38 |
- |
- |
9 |
17 |
33 |
| 36 |
200 |
.42 |
- |
8** |
12 |
20 |
37 |
| 36 |
250 |
.47 |
- |
10 |
14 |
23 |
40 |
| 36 |
300 |
.51 |
- |
12 |
17 |
25 |
42 |
| 36 |
350 |
.56 |
- |
15 |
19 |
28 |
45 |
| 42 |
150 |
.41 |
- |
- |
9 |
16 |
32 |
| 42 |
200 |
.47 |
- |
8 |
12 |
20 |
37 |
| 42 |
250 |
.52 |
- |
10 |
14 |
23 |
40 |
| 42 |
300 |
.57 |
- |
12 |
17 |
25 |
42 |
| 42 |
350 |
.63 |
- |
15 |
19 |
28 |
45 |
| 48 |
150 |
.46 |
- |
- |
9 |
17 |
33 |
| 48 |
200 |
.52 |
- |
8 |
12 |
20 |
37 |
| 48 |
250 |
.58 |
- |
10 |
14 |
23 |
40 |
| 48 |
300 |
.64 |
- |
12 |
17 |
25 |
42 |
| 48 |
350 |
.70 |
- |
15 |
19 |
28 |
44 |
| 54 |
150 |
.51 |
- |
- |
9 |
17 |
33 |
| 54 |
200 |
.58 |
- |
8 |
12 |
20 |
37 |
| 54 |
250 |
.65 |
- |
10 |
14 |
23 |
40 |
| 54 |
300 |
.72 |
- |
13 |
17 |
25 |
43 |
| 54 |
350 |
.79 |
- |
15 |
19 |
28 |
45 |
| 60 |
150 |
.54 |
- |
5** |
9 |
17 |
33 |
| 60 |
200 |
.61 |
- |
8 |
12 |
20 |
37 |
| 60 |
250 |
.68 |
- |
10 |
14 |
23 |
40 |
| 60 |
300 |
.76 |
- |
13 |
17 |
25 |
43 |
| 60 |
350 |
.83 |
- |
15 |
19 |
28 |
45 |
| 64 |
150 |
.56 |
- |
5** |
9 |
17 |
33 |
| 64 |
200 |
.64 |
- |
8 |
12 |
20 |
36 |
| 64 |
250 |
.72 |
- |
10 |
15 |
23 |
40 |
| 64 |
300 |
.80 |
- |
13 |
17 |
25 |
43 |
| 64 |
350 |
.87 |
- |
15 |
19 |
28 |
45 |
Notes:
** Minimum allowable depth of cover is 3'.
The bolded numbers denote the depths of cover resulting from the pipe thickness being governed by deflection in the design; these covers are greater due to the design deflection of 5% for flexible-lined pipe instead of 3% for cement-lined pipe.
|