American Ductile Iron Pipe Home Page

Flare Fittings

AMERICAN Ductile Iron Specials

Flange and Flare 90 Bends | Flare Castings


Flange and Flare
90° Bends

Flange and Flare 90 Bends | Flare Castings | To Top of Page

Short Radius

         

Long Radius

ADIP Table No. 7-12

Size
in.
Pressure
Rating
psi
T
in.
C
in.
Short Radius Long Radius
A
in.
B
in.
Weight
lb
A
in.
B
in.
Weight
lb
30 250 1.03 38.75 25 36 1950 - - -
36 250 1.15 46 28 38 2730 - - -
42 250 1.28 53 31 35 3200 - - -
48 250 1.42 59.5 34 46 5235 - - -
54 250 .90* 66.25 39 47.5 3540 - - -
60 250 .94* 73 43 54 4635 - - -
64 ** ** ** ** ** ** - - -

Notes:
* 54" and 60" castings have wall thicknesses that are per AWWA C153. All other wall thicknesses are per C100. See Table No. 7-3.
** Check AMERICAN for 64" Flare dimensions.
Since above fittings are not included in AWWA C110, A, B, and C dimensions above should be specified on engineering drawings.
Other joints can be furnished in lieu of flanges in some sizes.
See General Notes.


Flare+ Castings

Flange and Flare 90 Bends | Flare Castings | To Top of Page

Flange and Flare

ADIP Table No. 7-13

Size
in.
Pressure
Rating
psi
Dimensions in Inches Weight in Lbs (Min.Length)
T L C Flg & Flare MJ & Flare
4 250 0.52 8 9 40 -
6 250 0.55 8 11 65 -
8 250 0.6 10 13.5 105 -
10 250 0.68 10 16 145 -
12 250 0.75 12 19 210 -
14 250 0.66 12 21 240 -
16 250 0.7 16 23.5 310 -
18 250 0.75 16 25 370 -
20 250 0.8 18 27.5 435 -
24 250 0.89 18 32 680 -

MJ and Flare

ADIP Table No. 7-13 cont.

Size
in.
Pressure
Rating
psi
Dimensions in Inches Weight in Lbs (Min.Length)
T L
Minimum
L
Maximum
C Flg & Flare MJ & Flare
30 250 1.03 15 66 38.75 960 1080
36 250 1.15 14 66 46 1265 1435
42 250 1.28 12 72 53 1260 1430
48 250 1.42 18 72 59.5 2375 2625
54 250 .90* 19 72 66.25 1475 -
60 250 .94* 21 72 73 1935 -
64 ** ** ** ** ** ** -

Notes:
+ This fitting is sometimes referred to as "bell mouth."
* 54" and 60" castings have wall thicknesses that are per AWWA C153. All other wall thicknesses are per AWWA C100. See Table No. 7-3.
** Check AMERICAN for 64" Flare dimensions.
Flare castings can be furnished in a variety of lengths and with wall collars when specified. Flange or mechanical joint bell to be installed flush with the wall should be specified "tap for studs."
The addition of a wall collar to flare castings may affect the minimum length of the casting.
Other joints can be furnished in lieu of flanges or MJ bells in most sizes.
Since above fittings are not included in AWWA C110, L and C dimensions above should be specified on engineering drawings.
See General Notes.

 

 


 
 

© 1995 – 2008, American Cast Iron Pipe Company
Site Map | Contact Us