American Ductile Iron Pipe Home Page

Wall Sleeves and Wall Castings

AMERICAN Ductile Iron Specials
Mechanical Joint Wall Sleeves

MJ Wall Sleeve

 

MJ and PE
Wall Sleeve

     
*T1 for:
4"-12" = .50
14"-24" = .75
30"-36" = 1.00
42"-48" = 1.25
  Increments of sleeve
lengths available:
4"-24" = 1"
30"-54" = 2"

ADIP Table No. 7-1

Size
in.
Rating
psi
T
Wall
Thickness
in.
C
Collar
Diameter
in.
Collar
Weight
lb
Weight
per 1"
Increment
of Length+
lb
MJ Wall Sleeve MJ & PE Wall Sleeve
Lengths
Min.-Max.
in.
Weight
of 12" lg.
Sleeve
lb
Lengths
Min.-Max.
in.
Weight
of 12" lg.
Sleeve
lb
4 350 0.52 9 5 2.5 8"-20" 50 8"-20" 45
6 350 0.55 11 6 3.6 8"-20" 70 8"-20" 60
8 350 0.6 13.25 8 5 8"-30" 95 8"-30" 80
10 350 0.68 15.5 9 6.8 8"-30" 125 8"-30" 105
12 350 0.75 17.75 11 8.8 8"-30" 160 8"-30" 135
14 350 0.66 20.25 21 8.9 8"-34" 190 8"-36" 160
16 350 0.7 22.5 24 10.6 8"-34" 230 8"-36" 190
18 350 0.75 24.75 27 12.7 8"-34" 275 8"-36" 225
20 350 0.8 27 30 15 8"-34" 310 8"-36" 260
24 350 0.89 31.5 37 19.7 8"-34" 405 8"-36" 335
30 250 1.03 39 73 28.3 10"-24" 620 10"-24" 510
36 250 1.15 45.75 87 37.8 10"-24" 835 10"-24" 690
42 250 1.28 53 149 48.6 10"-24" 1115 10"-24" 920
48 250 1.42 59.75 170 61.5 10"-24" 1370 10"-24" 1140
**54 250 1.55 65.5 184 73.9 12"-24" 1375 12"-24" 1225

Notes:
*This thickness will vary slightly because of manufacturing process.
**The 54" Mechanical Joint Wall Sleeve is special with special mechanical joint (gland weight: 360 lbs each; gasket weight: 7 lbs each; 36-1 1/4" X 6" stud bolts each with one hex nut and weighing 3.4 lbs each). Consult AMERICAN for additional information on this special sleeve and for information on 60" & 64" wall sleeves.
Some sizes of wall sleeves in shorter lengths than shown can be furnished by special pattern adaption. Check AMERICAN if required.
+This "Weight per 1" Increment of Length" is the weight to add to -- or subtract from -- the weight of the 12"-long wall sleeve for each 1" variation in sleeve length from 12".
Sleeves will be furnished tapped for studs. Wall collar will be furnished approximately in center unless otherwise specified. Minimum distance from the sleeve end to the center of the collar is 4" for 4"-24" sizes, 5" for 30"-60". For sizes 4"-24", wall collar can be positioned on sleeve in 1" increments; for sizes 30"-54" in 2" increments.
Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of item inside steel forms, this must be specified on order.
See General Notes.


AMERICAN Ductile Iron Specials
Plain End Spool and Integrally Cast Wall Collar Weights
Statically Cast Wall Castings

ADIP Table No. 7-3

Size
in.
Plain End Spools Wall Collars
Ductile Iron Statically Cast Integrally Cast
AWWA C100* Class B AWWA C100* Class D T1
Thickness
in.
C
Diameter
in.
Weight
lb
T
Thickness
in.
Weight
lb/ft
T
Thickness
in.
Weight
lb/ft
4 - - 0.52 22.8 0.5 8 5
6 - - 0.55 35.3 0.5 10 6
8 - - 0.6 51.2 0.5 12.5 9
10 - - 0.68 71.5 0.5 14.5 10
12 - - 0.75 93.7 0.5 16.5 12
14 0.66 94.7 0.82 119.2 0.75 19.5 26
16 0.7 114.6 0.89 147.5 0.75 21.75 30
18 0.75 137.8 0.96 178.4 0.75 23.75 33
20 0.8 163.1 1.03 212.3 0.75 25.75 35
24 0.89 217.3 1.16 286.1 0.75 30.25 45
30 1.03 312.7 1.37 421.3 1 36.5 70
36 1.15 418.8 1.58 582 1 43 88
42 1.28 542.3 1.78 764.2 1.25 49.5 130
48 1.42 687.3 1.96 961 1.25 56.5 172
54 1.55 851 2.23 1226.5 1.5 63 201
60 1.1 652.4 - - 1.5 70.25 345
64 1.16 733.5 - - 1.5 74.88 395

Notes:
*See Section 12, Table No. 12-1 for the obsolete AWWA C100 class thicknesses.
For weight of the 8" length of 4"-48" plain end on fitting per AWWA C110 gauged for MJ, see Section 5, Table No. 5-2.


AMERICAN Ductile Iron Specials
Wall Casting Lengths - Statically Cast**
Maximum Laying and Overall Lengths

ADIP Table No. 7-6

Type
Joints
Size
in.
Maximum Statically Cast Lengths
Laying Lengths
ft.-in.
Overall Lengths
ft.-in.
SKT Depth
MJ-W/C-MJ 30"-36" 5'-0" 5'-8" 4
MJ-W/C-MJ 42"-48" 6'-0" 6'-8" 4
Fastite-W/C- Fastite 14"-20" 3'-0" 3'-9" 4.5
Fastite-W/C- Fastite 24" 5'-0" 5'-9 1/2 " 4.75
Fastite-W/C- Fastite 30"-36" 5'-0" 5'-10 1/2 " 5.25
Fastite-W/C- Fastite 42" 5'-6" 6'-8" 7.5
Fastite-W/C- Fastite 48" 5'-6" 6'-10" 8
Fastite-W/C- Fastite 54" 5'-6" 6'-11" 8.5
Fastite-W/C- Fastite 60" 5'-6" 6'-11 1/2" 8.75
Fastite-W/C- Fastite 64" 5'-6" 7'-0" 9
Flange-W/C-Flange 30"-36" 5'-6" 5'-6" -
Flange-W/C-Flange 42"- 64" 6'-0" 6'-0" -
MJ-W/C-Flange &MJ-W/C-Plain End 30"- 36" 5'-0" 5'-4" 4
MJ-W/C-Flange &MJ-W/C-Plain End 42"-48" 6'-0" 6'-4" 4
Fastite-W/C-Flange 30"-36" 5'-0" 5'-5 1/4" 5.25
Fastite-W/C-Flange 42" 6'-0" 6'-7 1/2" 7.5
Fastite-W/C-Flange 48" 6'-0" 6'-8" 8
Fastite-W/C-Flange 54" 6'-0" 6'-8 1/2" 8.5
Fastite-W/C-Flange 60" 6'-0" 6'-8 3/4" 8.75
Fastite-W/C-Flange 64" 6'-0" 6'-9" 9
Flex Ring-W/C-Flex Ring 14"-16" 3'-0" 4'-2 3/4" 7.38
Flex Ring-W/C-Flex Ring 18"-20" 3'-0" 4'-4 3/4" 8.2
Flex Ring-W/C-Flex Ring 24" 4'-6" 5'-11 15/16" 8.96
Flex Ring-W/C-Flex Ring 30"-36" 4'-6" 6'-0 3/4" 9.38
Flex Ring-W/C-Flex Ring 42" 4'-6" 6'-3 5/8" 10.84
Lok Ring-W/C-Lok Ring 42"-54" 4'-6" 6'-2 1/4" 10.07
Lok Ring-W/C-Lok Ring 60"-64" 4'-6" 6'-3 1/4" 10.57
Lok Ring-W/C-Flange 42"-54" 5'-6" 6'-4 1/8" 10.07
Lok Ring-W/C-Flange 60"-64" 5'-6" 6'-4 1/2" 10.57

Notes:
All lengths of Plain End-Thrust Collar-Plain End Wall Pipe are fabricated from centrifugally cast ductile iron pipe.
For minimum lengths see Table No. 7-7 (below).
To determine weight of any wall casting not listed in Table No. 7-8 (below), use data in Table No. 7-3 (above).
Fastite-W/C-Fastite Wall Castings are only available as static castings. All other combinations of joints can be fabricated from centrifugally cast ductile iron pipe with thrust collars as required. See Table No. 7-5.
Correctly installed flanged wall pipe will normally have the bolt holes straddling the horizontal and vertical center lines. Checking with a spirit level or plumb line prior to pouring the walls is recommended.
"W/C" in the description of wall castings refers to wall collar. Wall collar dimensions are shown in Table No. 7-3 (above).
**Most wall pipes will be furnished fabricated from centrifugally cast ductile iron pipe. The statically cast lengths shown in this table may not be readily available.


AMERICAN Ductile Iron Specials
Wall Castings - Statically Cast**
Minimum Overall Lengths

ADIP Table No. 7-7

Size
in.
Minimum Overall Lengths in Inches
MJ-
W/C-
MJ+
Fst-
W/C-
Fst
Flg-
W/C-
Flg
MJ-
W/C-
Flg*
Fst-
W/C-
Flg*
MJ-
W/C-
PE*
FR-***
W/C-
FR
LKR-***
W/C-
LKR
LKR-***
W/C-
Flg
14 14 15 - - - - 20 - -
16 13 15 - - - - 20 - -
18 13 15 - - - - 21 - -
20 13 15 - - - - 21 - -
24 15 18 - - - - 25 - -
30 17 20 14 17 20 17 26 - -
36 17 20 14 17 20 17 26 - -
42 17 27 15 17 20 17 29 28 21
48 17 27 15 17 20 17 - 28 22
54 - 27 16 - 21 - - 26 23
60 - 28 18 - 23 - - 27 23
64 - 28 20 - 23 - - 28 23

Notes:
*Minimum overall lengths for castings with one MJ bell or one Fastite bell are based on the wall collar being located in the center of the overall length. Where the wall collar can be located off-center, away from the socket, some reduction can generally be made in the minimum length.
**Most wall pipes will be furnished fabricated from centrifugally cast ductile iron pipe. The statically cast lengths shown in this table may not be readily available.
***Flex-Ring and Lok-Ring Wall Castings are not illustrated.
Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of item inside steel forms, this must be specified on order.
Some sizes of wall pipe in shorter lengths than shown can be furnished by special pattern adaptation. Check AMERICAN if required.
"W/C" in the description of wall castings refers to wall collar. Wall collar dimensions are shown in Table No. 7-3 (above).
Correctly installed flanged wall pipe will normally have the bolt holes straddling the horizontal and vertical centerlines. Checking with a spirit level or plumb line prior to pouring the walls is recommended.
+Mechanical joint end wall sleeves are available in some sizes with shorter lengths than statically cast wall pipe per this table (see Table 7-1 above).


AMERICAN Ductile Iron Specials
Mechanical Joint and Fastite Wall Castings - Statically Cast**

MJ-W/C-MJ

 

Fastite-W/C-Fastite

ADIP Table No. 7-8

Size
in.
Pressure
Rating
psi
T
Wall
Thickness
in.
L
Overall
Length
in.
Min./Max
A
Depth
Socket
(MJ)
in.
B
Depth
Socket
(Fst)
in.
Weight in Pounds*
MJ-W/C-MJ Fst-W/C-Fst
14 250 0.66 14 - 4 1/2 - 310
14 250 0.66 45 - 4 1/2 - 500
16 250 0.7 13 3 1/2 - 280 -
16 250 0.7 15 - 4 1/2 - 315
16 250 0.7 43 3 1/2 - 570 -
16 250 0.7 45 - 4 1/2 - 600
18 250 0.75 13 3 1/2 - 335 -
18 250 0.75 15 - 4 1/2 - 355
18 250 0.75 43 3 1/2 - 680 -
18 250 0.75 45 - 4 1/2 - 700
20 250 0.8 13 3 1/2 - 390 -
20 250 0.8 15 - 4 1/2 - 395
20 250 0.8 43 3 1/2 - 795 -
20 250 0.8 45 - 4 1/2 - 800
24 250 0.89 15 3 1/2 - 545 -
24 250 0.89 18 - 4 3/4 - 605
24 250 0.89 67 3 1/2 - 1485 -
24 250 0.89 69.5 - 4 3/4 - 1540
30 250 1.03 17 4 - 905 -
30 250 1.03 20 - 5 1/4 - 1000
30 250 1.03 68 4 - 2235 -
30 250 1.03 70.5 - 5 1/4 - 2315
36 250 1.15 17 4 - 1290 -
36 250 1.15 20 - 5 1/4 - 1385
36 250 1.15 68 4 - 3070 -
36 250 1.15 70.5 - 5 1/4 - 3150
42 250 1.28 17 4 - 1655 -
42 250 1.28 20 - 7 1/2 - 1090
42 250 1.28 80 4 - 4500 -
42 250 1.28 80 - 7 1/2 - 3805
48 250 1.42 17 4 - 2120 -
48 250 1.42 20 - 8 - 1360
48 250 1.42 80 4 - 5730 -
48 250 1.42 82 - 8 - 4910
54 250 1.55 20 - 8 1/2 - 1690
54 250 1.55 83 - 8 1/2 - 6160
60 250 1.1 20 - 8 3/4 - 1925
60 250 1.1 83.5 - 8 3/4 - 5380
64 250 1.16 20 - 9 - 2165
64 250 1.16 84 - 9 - 6075

Notes:
*Weights are shown only for minimum and maximum lengths. Weights for intermediate lengths can be calculated from data in Table No. 7-3 (above).
The size, pressure rating, overall length and location of wall collar need to be specified when ordering. Wall collars will be located at the center of the overall length of the pipe, unless otherwise specified. Any lengths between minimum and maximum shown above can be furnished.
Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of item inside steel forms, this must be specified on order.
Where tie rods to connecting fitting are required for use with MJ Wall Pipe, the bell(s) of the wall pipe and the connecting fitting should be specifically ordered and installed with the bolt holes straddling the vertical centerlines.
When flanges or mechanical joint bells are to be flush with the wall, specify "tap for studs."
See Table No. 7-3 (above) for wall collar dimensions.
**Most wall pipes will be furnished fabricated from centrifugally cast ductile iron pipe. The statically cast lengths shown in this table may not be readily available.
See General Notes.


 
 

© 1995 – 2008, American Cast Iron Pipe Company