ACIPCO DUCTILE IRON SPECIALS
ACIPCO can furnish tangential welded-on outlets in certain diameters. Pipe with tangential outlets can be rotated with the outlets on bottom for blow-offs, or on top for air release. The parent pipe and outlet pipe can be furnished with the ACIPCO FastiteĀ® or flanged joint ends; however, flanged ends are not recommended for tangential outlets. Minimum classes and location of outlets are the same as for regular welded-on outlets. This is a shop product and is not intended for field fabrication. Parent and outlet pipe are normally furnished cement lined in accordance with ISO 4179. Contact ACIPCO if linings other than cement linings are required.

|
INT ACIPCO DUCTILE IRON WELDED-ON TANGENTIAL OUTLETS
|
ACIPCO DUCTILE IRON WELDED-ON TANGENTIAL OUTLETS
|
Parent
Pipe
Diameter
(mm)
|
Maximum
Outlet
Diameter
(mm)
|
Nominal
Thickness
Parent Pipe
(mm)
|
J
Socket
Outlet
(mm)
|
J
Flanged
Outlet
(mm)
|
Ā
Outlet
Diameter
(mm)
|
Nominal
Thickness
Outlet Pipe
(mm)
|
Rated
Working
Pressure
(Bar)
|
B
Min. Distance
to Pipe End
(mm)
|
| 250 |
150 |
9 |
318 |
318 |
150 |
7.8 |
16 |
375 |
| 300 |
200 |
9.6 |
343 |
343 |
200 |
8.4 |
16 |
425 |
| 350 |
200 |
10.2 |
368 |
368 |
- |
- |
- |
- |
| 400 |
250 |
10.8 |
394 |
394 |
250 |
9 |
16 |
450 |
| 450 |
300 |
11.4 |
419 |
419 |
300 |
9.6 |
16 |
500 |
| 500 |
350 |
11 |
445 |
445 |
350 |
10.2 |
16 |
575 |
| 600 |
400 |
12.1 |
508 |
508 |
400 |
10.8 |
16 |
650 |
| 700 |
450 |
13.2 |
559 |
559 |
450 |
11.4 |
16 |
725 |
| 800 |
500 |
14.3 |
610 |
610 |
500 |
11 |
16 |
800 |
| 900 |
600 |
15.4 |
660 |
660 |
600 |
12.1 |
16 |
950 |
| 1000 |
700 |
16.5 |
711 |
711 |
700 |
13.2 |
16 |
1100 |
| 1200 |
800 |
18.7 |
838 |
838 |
800 |
14.3 |
16 |
1275 |
| 1400 |
800 |
20.9 |
953 |
853 |
800 |
14.3 |
16 |
1275 |
| 1500 |
800 |
22 |
1003 |
1003 |
800 |
14.3 |
16 |
1275 |
| 1600 |
800 |
23.1 |
1054 |
1054 |
800 |
14.3 |
16 |
1275 |
Notes:
Contact ACIPCO for larger diameter tangential outlets or for smaller parent pipe size requirements, if needed. The maximum outlet diameter is the same as shown for welded-on outlets in the table on the Ductile Iron Specials - Welded-On Outlets page. The "J" dimension shown above varies, depending on the parent pipe/outlet size chosen. Please contact ACIPCO if this dimension is needed.
|